Thursday, March 18, 2010

Substation main earth bar pictures

You will find below a few pictures of HV electrical substation’s main earth bar. I took these pictures inside a Consumer HV room at one of my recent building projects.

Picture 1 – Location of the main earthing bar inside a HV Switchgear Room




Observe the location and position of the main earth bar in the HV room. At every electrical room of significant size, at least one main earth bar like this should be provided.

Picture 2 below shows a closer view of this earth bar.

=================
RELATED ARTICLES:
Exothermic welding: Cable to cable connectionsElectrical grounding  | Electrical Grounding Electrode Pictures  | Switchboard earthing picturesLightning roof conductor installationLightning Earth Rods Installation | Temporary Electrical Earthing Pictures | Electrical installation pictures
=================

Picture 2 – HV Room’s main earth bar



The purpose of having the main bar is simple.

All earthing conductors inside the HV room would be connected to this bar. That is the reason you can see in Picture 2 a number of ready-made termination holes complete with bolts, nuts and spring washers.

Notice the main copper earthing tape mounted along the substation wall in Picture 1. This is the main equipotential earthing conductor for this electrical room.

It should run through all perimeter walls of the room at a height of approximately 12 inch from the substation’s finish floor level. That is why you can see that in Picture 2 the left-most and right-most terminals have been connected with a horizontal copper tape conductor.

An ideal installation would have the main equipotential conductor run in a ring around the perimeter walls and both conductor ends connects to the main earth bar at the left-most and right-most terminals.

However, in this case it was not in a ring at the time this picture was taken because there was an entrance door at the wall in front of the 11 KV switchgear. Picture 1 was taken at the rear.

Later the horizontal copper tapes were connected into a ring by running additional conductor above the entrance door.

What are the conductors connected to the main earth bar in Picture 2?

The horizontal tapes at the left and right are what I have explained above.

The other three conductors have been installed vertically down into the cable trench.

(NOTE: Notice that the cable trench has been filled with river sand. Many installations prefer to have cable trenches filled with sand to avoid problems with rates and snakes playing hide and seek inside the cable trench.

Once a while these live beings find their way into the electrical switchgears and cause many problems including short circuits and intermittent trippings.

I have come across many operational problems because of these reasons.

To overcome these problems, many operation engineers prefer to just have all substation cable trenches filled with river sand. Then the trench is finished with approximately one inch of lean concrete on top of the sand and level with the substation floor.

When they need to do some work in the trench, they just knock down and break the thin concrete and dig out the sand.

No doubt this is a messy way of doing things, but it seemed to have been a very practical solution to these sorts of problems.)

Back to the earth tapes run vertical down into the cable trench. Where are these tape conductors for?

From the right, the first vertical conductor is connected to the HV switchgear equipotential conductors.

The center vertical conductor is connected to the earth busbar inside the switchgear compartments.

The last vertical conductor, at the far left, is the connection to the earthing electrodes outside the HV room.

Picture 3 – Disconnecting earth terminals



Some of the readers may not notice that the earth bar in Picture 2 is actually a two-piece bar. The two separate pieces are much more visible in Picture 3 above.

Notice that there is just one terminal (other than the terminal for connecting the two bars) on the short piece, while there are six terminals on the longer bar.

This has been designed to be so. The terminal on the short bar is called “disconnecting terminal”. The whole assembly is purchased readily assembled by manufacturer.

Usually earth bar with one or two disconnecting terminals are readily available. If an electrical contractor needs more disconnecting terminals, then it need to be ordered and it would be fabricated as required by the project at hand.

The terminals on the shorter piece are intended for testing and trouble-shooting purposes. That is why the conductor to the grounding electrodes is often connected to the short piece.

However, so clients forbid the use of the disconnecting terminals altogether. These sorts of clients usually manage many separate electrical installations with separate local operation teams.

It is usually not always easy to ensure an adequate level of competency of each member of the local operation and maintenance teams.

An earth lead conductor connected to the disconnecting terminal may easily lead to a total absence of connection to the earth electrode.

This presents a very serious safety risk.

This lead to a policy of forbidding the use of the disconnecting terminals. Therefore, all their substations would have single-piece earth bars.

Picture 4 – HV switchgear body earth conductor



This photo gives a clearer view of the switchgear equipotential bonding conductor.

As you may be aware, the switchgear came in separate smaller panels and the individual panels are then connected and bolted together at site.

The switchgear body earth (another name for the enclosure equipotential bonding) conductors, as indicated in Picture 4, have also been installed and bolted to each individual panel.

Therefore, these individual lengths of body earth conductors are connected and bolted to each other at the construction site.

The short inter-connecting copper pieces and all accessories including bolt-and-nuts for making the complete connection are provided by the switchgear manufacturer and shipped together with the rest of the panels.

Picture 5 – Bolt, nut and spring washer



This may be obvious for most readers, but some beginners may be silently screaming for help. So I labeled these components for them since they are such critical components in the electrical grounding system.

Picture 6 – Earth bar insulator post





Copyright http://electricalinstallationwiringpicture.blogspot.com Substation main earth bar pictures

Sunday, February 21, 2010

Electrical Grounding Electrode Pictures

The following pictures show examples of grounding electrodes and earthing chambers for electrical earthing systems.

Picture 1 – Earthing chambers



=== RELATED ARTICLES:  Exothermic welding: Cable to cable connections | Electrical grounding  | Substation main earth bar pictures  | Switchboard earthing picturesLightning roof conductor installationLightning Earth Rods Installation | Temporary Electrical Earthing Pictures | A simple electrical installation | Electrical socket extension unit  | 1- Phase ELCB connection pictures  | Bare fluorescent light pictures  | Recessed down lights installation  | Bollard light pictures  | Light switch installation pictures  | Home wiring pictures  | Electric Meters  | Most Basic Principles of House Wiring | MATV antenna bracket pictures | Electrical installation pictures |   Temporary electrical installation pictures |  Temporary lighting installation pictures

=================

Grounding electrodes are driven several feet into the ground soil using a hammer or powered rod driver tools.

The connection is made at the top of each electrode to the earthing conductor coming from the electrical equipment to be grounded, or the down conductor of the lightning protection system.

This connection must be protected and it should be available for inspection and servicing in the future. It is therefore enclosed inside a chamber that is provided with a removable cover so that the grounding connection is easily accessible.

Picture 1 above is an example of the earthing chambers. This one is one of the smaller-sized types, approximately 8 inch by 8 inch of internal clearance inside the square chamber. Some designs are bigger.

Picture 2 below shows the same grounding chamber with the cover removed. Notice the strong metal pull eye provided to help removal of the cover. The earth chamber is installed in the ground and over time the gaps between the cover and the chamber are eventually filled with dirt, sand and soils. This makes the opening of the cover very difficult sometimes.

Picture 2 – The earthing chamber with the cover removed



What you can see inside the chamber in Picture 2 is the earthing copper tape that has been bonded to the grounding electrode. Picture 3 shows the bonding this better.

Picture 3 – Another view of the grounding chamber



Picture 4 – Closer view of the grounding rod



I have attached a diagram (see Diagram 5 below) that gives an overall picture of the installation of the electrical grounding electrode.

Diagram 5 – Grounding electrode and earth chamber



From the diagram you can see how the earthing copper tape is installed below ground and enter the grounding chamber from below. Then the end of the copper tape is connected to the top of the electrode using a clamp.

However the copper tape connection to the earth rod in the above pictures does not use a clamp. That is why you cannot see any sign of a clamp in the picture.

The earthing connection in this case uses thermo-weld bonding. That is the reason you can see the copper see to connect to the vertical rod at ninety-degree angle. The thermo-weld joint can be done much easier in this formation.

Whether the choice is to use the compression clamp or the thermo-weld bonding is a matter of choice depending on the number of factors.

Properly done, the thermo-weld joint is virtually maintenance free. You would not even need the inspection chamber, even though it is better to have one because you may need to make more connections to the grounding rod in the future.

The joint made by the compression clamp, on the other hand, need to be inspected regularly at certain intervals to make sure there is no interference to the joints. The earthing resistance test also need to be tested every one or two year to ensure it is within the acceptable level.

A total earthing resistance that is too high will present a serious shock hazard to users of the electricity within the premise concerned.

The pictures below show joints of earthing conductors to grounding rods.

Picture 6 – Copper tape to earthing electrode connection



Some readers may ask where the earthing chamber in this picture is.

Actually the installation here has not yet been completed. I have allowed the contractor to proceed with the earthing installation so they can energize the power supply early.

The earthing chamber would be installed later after the roadwork is ready for the installation of the earthing chambers. This particular earth chamber was actually installed near the road curb of the internal road. Try to avoid this if you can.

Picture 7 below shows a broader view of the electrode



As you can see, the connection and part of the electrode seems too high above the ground. Actually that would be the real finished level of the internal road which was still under construction. That was the reason the earthing chamber was not installed yet.

Picture 8 – Earthing copper cable connection to earth rod



Picture 8 above shows another earthing connection inside the earth chamber using the compression type brass clamp.

Observe that the top end of the electrode in this picture does not have the screw thread that is clearly visible in the electrode of Picture 6.

That is because the real top end of the earth rod in Picture was much higher but it was cut to match the expected final ground level.

Copyright http://electricalinstallationwiringpicture.blogspot.com Electrical Grounding Electrode Pictures